- Siemens
- ABB
-
A-B
- MTL
- Pepperl Fuchs
- Phoenix
- Weidmuller
-
IFM
-
Hirschman
-
Hach
-
Schneider
- Norgren
- Fluke
- Sick
- Moxa
- Honeywell
- Yokogawa
- Rosemount
- Emerson
- Beamex
- Festo
- Oring
- Danfoss
- Rotork YTC
- Atlas Copco
-
Allen Bradley
-
YASKAWA
- Triconex
-
Endress+Hauser
-
Dungs
- Belimo
-
Jaquet
-
WIKA
-
UE
- Foxboro
- SMC
-
bifold
-
Nagano Keiki
-
AIRTAC
-
Dynisco
-
proface
-
Woodward
-
CPC
-
Durag
-
Crowcon
-
Bently Nevada
- Krohne
- York
- Bray
-
B&R
- MSA
- AZBIL
- Omron
-
PEPPER+FUCHS
-
MEANWELL
- GE
- XECRO
-
KONAN
-
Fairford
-
testo
-
Emotron
- PR electronics
MTL5541/S -T REPEATER POWER SUPPLY
MTL5541/S -T REPEATER POWER SUPPLY
The MTLx541 provides a fully-floating dc supply for energising a conventional 2- or 3-wire 4/20mA transmitter, which is located in a hazardous area, and repeats the current in another floating circuit to drive a safe-area load. For HART 2-wire transmitters, the unit allows bi-directional communications signals superimposed on the 4/20mA loop current. Alternatively, the MTLx541S acts as a current sink for a safe-area connection rather than driving a current into the load.Separately powered current sources, such as 4-wire transmitters, can be connected but will not support HART communication.
MTL5541/S -T REPEATER POWER SUPPLY
MTL5541/S -T REPEATER POWER SUPPLY
SPECIFICATION
See also common specification
Number of channels
One
Location of transmitter
Zone 0, IIC, T4–6 hazardous area if suitably certified
Div. 1, Group A hazardous location
Safe-area output
Signal range: 4 to 20mA
Under/over-range: 0 to 24mA
Safe-area load resistance (MTLx541)
@ 24mA: 0 to 360Ω
@ 20mA: 0 to 450Ω
Safe-area load (MTLx541S)
Current sink: 600Ω max.
Maximum voltage source: 24V dc
Safe-area circuit output resistance: > 1MΩ
Safe-area circuit ripple
< 50µA peak-to-peak
Hazardous-area input
Signal range: 0 to 24mA (including over-range)
Transmitter voltage: 16.5V at 20mA
Transfer accuracy at 20°C
Better than 15µA
Temperature drift
< 0.8µA/°C
Response time
Settles to within 10% of final value within 50µs
Communications supported
HART (terminals 1 & 2 only)
MTL5541/S -T REPEATER POWER SUPPLY
These models have been assessed for use in IEC 61508 functional safety applications.SIL2 capable for a single device (HFT=0) SIL3 capable for multiple devices in safety redundant configurations (HFT=1) See data on MTL web site and refer to the safety manual.