SMART Current Driver KFD2-SCD2-Ex1.LK PEPPERL FUCHS
SMART Current Driver KFD2-SCD2-Ex1.LK PEPPERL FUCHS
·1-channel isolated barrier
·24 V DC supply (Power Rail)
·Current output up to 650 Ω load
·HART I/P and valve positioner
·Line fault detection (LFD)
·Accuracy 0.1 %
·SIL 2 (SC 3) acc. to IEC/EN 61508
SMART Current Driver KFD2-SCD2-Ex1.LK PEPPERL FUCHS
Function
This isolated barrier is used for intrinsic safety applications.
The device drives SMART I/P converters, electrical valves, and positioners in hazardous areas.
Digital signals are superimposed on the analog values at the field side or control side and are transferred bi-directionally.
Current transferred across the DC/DC converter is repeated at terminals 1 and 2. Terminals 2 and 3 are used when no short circuit detection is required.
An open or short field circuit presents a high impedance to the control side to allow alarm conditions to be monitored by the control system.
If the HART communication resistance in the loop is too low, the internal resistance can be used.
Test sockets for the connection of HART communicators are integrated into the terminals of the device.
A fault is signalized by LEDs and a separate collective error message output.
SMART Current Driver KFD2-SCD2-Ex1.LK PEPPERL FUCHS
Technical Data
General specifications
Signal type Analog output
Functional safety related parameters
Safety Integrity Level (SIL) SIL 2
Systematic capability (SC) SC 3
Supply
Connection Power Rail or terminals 14+, 15-
Rated voltage Ur 19 ... 30 V DC
Ripple ≤ 10 %
SMART Current Driver KFD2-SCD2-Ex1.LK PEPPERL FUCHS
Technical Data
Rated current Ir ≤ 30 mA at 24 V
Power dissipation ≤ 600 mW at 20 mA and 500 Ω load
Power consumption ≤ 700 mW
Input
Connection side control side
Connection terminals 7-, 8+, (9+)
Input signal 4 ... 20 mA , limited to approx. 30 mA
Input voltage open loop voltage of the control system ≤ 30 V
Voltage drop approx. 6 V at 20 mA
Input resistance field wiring open circuit : > 100 kΩ
field wiring < 50 Ω : > 100 kΩ when using terminals 1 and 2
Output
Connection side field side
Connection terminals 1+, 2-
terminals 3+, 2- (no short circuit detection)
Voltage ≥ 13 V at 20 mA
Current 4 ... 20 mA
Load 100 ... 650 Ω , for terminals 1, 2
0 ... 550 Ω , for terminals 2, 3
Ripple 20 mV rms
Line fault detection breakage, load > 100 kΩ, short-circuit, load < 50 Ω
Fault indication output
Output type open collector transistor (internal fault bus)
Transfer characteristics
Deviation at 20 °C (68 °F), 4 ... 20 mA
< 0.1 % of full scale, incl. non-linearity and hysteresis
Influence of ambient temperature < 2 µA/K (-20 ... 70 °C (-4 ... 158 °F)); < 4 µA/K (-40 ... -20 °C (-40 ... -4 °F))
Frequency range field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
control side into the field side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
Rise time 10 to 90 % ≤ 10 ms
Galvanic isolation
Input/Output basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input/power supply basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Indicators/settings
Display elements LEDs
Labeling space for adhesive label at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibility NE 21:2017
EN 61326-3-2:2018
Degree of protection IEC 60529
Protection against electrical shock UL 61010-1:2012
Ambient conditions
Ambient temperature -40 ... 70 °C (-40 ... 158 °F)
Mechanical specifications
Degree of protection IP20
Connection screw terminals
Mass approx. 115 g
Dimensions 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) , housing type B2
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificate BAS 00 ATEX 7240 X
SMART Current Driver KFD2-SCD2-Ex1.LK PEPPERL FUCHS