-
Siemens
-
Siemens Siprotec 7SK...
-
Siemens Siprotec 7UT...
-
Siemens Siprotec 7SL...
-
Siemens Siprotec 7SA...
-
Siemens Siprotec 7SD...
-
Siemens Simatic ET 2...
-
Siemens Siprotec 7SJ...
-
Siemens Power Contac...
-
Siemens Temperature ...
-
Siemens spare parts
-
Siemens motors
-
Siemens Positioner
-
Siemens Drives
-
Siemens PLC
-
Siemens Transmitter
-
Siemens Siprotec 7SK...
- Yokogawa
- Phoenix
- Hirschman
- Honeywell
- ABB
- MTL
- Pepperl Fuchs
-
Schneider
- Emerson
- Weidmuller
- Moxa
-
Endress+Hauser
-
Allen Bradley
-
Mitsubishi
-
IFM
-
SEW
-
Hach
- Norgren
- Fluke
- Danfoss
- Sick
-
A-B
- Rosemount
- Beamex
- Festo
- Oring
- Rotork YTC
- Atlas Copco
-
YASKAWA
- Triconex
-
Dungs
- Belimo
-
Jaquet
-
WIKA
-
UE
- Foxboro
- SMC
-
bifold
-
Nagano Keiki
-
AIRTAC
-
Dynisco
-
proface
-
Woodward
-
CPC
-
Durag
- Krohne
- York
- Bray
-
B&R
- MSA
- AZBIL
- Omron
-
PEPPER+FUCHS
-
MEANWELL
-
Crowcon
- GE
- XECRO
-
KONAN
-
Fairford
-
testo
-
Bently Nevada
-
Emotron
- PR electronics
Rail-Mount Temperature Transmitter ABB TTR200
Rail-Mount Temperature Transmitter ABB TTR200
SIL functional safety
With conformity according to IEC 61508 for the use in safety relevant applications up to and including SIL 3 (redundant).
• In the use of one transmitter the device fulfills the requirements according to SIL 2.
• In the use of redundant handled transmitters the requirements can be fulfilled according to SIL 3.
Instructions on this can be found in the SIL-Safety Manual.
Rail-Mount Temperature Transmitter ABB TTR200
Input - resistance thermometer /resistances
Resistance thermometer
• Pt100 in accordance with IEC 60751, JIS C1604,
MIL-T-24388
• Ni in accordance with DIN 43760
• Cu in accordance with recommendation OIML R 84
Resistance measurement
• 0 to 500 Ω
• 0 to 5000 Ω
Sensor connection type
Two-, three-, four-wire circuit
Rail-Mount Temperature Transmitter ABB TTR200
Connection lead
• Maximum sensor line resistance per line 50 Ω in accordance with NE 89
• Three-wire circuit:Symmetrical sensor line resistances
• Two-wire circuit:Compensation up to 100 Ω total lead resistance
Rail-Mount Temperature Transmitter ABB TTR200
Measurement current
< 300 μA
Sensor short circuit
< 5 Ω (for resistance thermometer)
Sensor wire break
• Measuring range: 0 to 500 Ω > 0.6 to 10 kΩ
• Measuring range: 0 to 5 Ω > 5.3 to 10 kΩ
Corrosion detection in accordance with NE 89
• Three-wire resistance measurement > 50 Ω
• Four-wire resistance measurement > 50 Ω
Sensor error signaling
• Resistance thermometer:
Sensor short circuit and sensor wire break
• Linear resistance measurement:
Sensor wire break
Rail-Mount Temperature Transmitter ABB TTR200