MTL4541 1channel 2/3 wire Transmitter repeater England origin safe isolator
- Product Name:MTL4541 1channel 2/3 wire Transmitter repeater England origin safe isolator
- Product Number:MTL4541
- Brand:MTL
- Views:224
-
MTL4541 1channel 2/3 wire Transmitter repeater England origin safe isolator
的详细介绍Product overview
MTL4541 1channel 2/3 wire Transmitter repeater England origin safe isolator
MTL4541 1 channel 2/3 wire Transmitter repeater England origin safe isolator
MTL4541 product specification as below for your reference.
MTL4541 1channel 2/3 wire Transmitter repeater England origin safe isolator
MTL4541/S –
MTL5541/S REPEATER POWER SUPPLY 4/20mA, HART®, 2- or 3-wire transmitters The
MTLx541 provides a fully-floating dc supply for energising a conventional 2- or
3-wire 4/20mA transmitter, which is located in a hazardous area, and repeats
the current in another floating circuit to drive a safe-area load. For HART
2-wire transmitters, the unit allows bi-directional communications signals
superimposed on the 4/20mA loop current. Alternatively, the MTLx541S acts as a
current sink for a safe-area connection rather than driving a current into the
load. Separately powered current sources, such as 4-wire transmitters, can be
connected but will not support HART communication.
SPECIFICATION
MTL4541 1channel 2/3 wire Transmitter repeater England origin safe isolator
See also common
specification
Number of
channels
One
Location of
transmitter
Zone 0, IIC,
T4–6 hazardous area if suitably certified
Div. 1, Group A
hazardous location
Safe-area
output
Signal range: 4
to 20mA
Under/over-range:
0 to 24mA
Safe-area load
resistance (MTLx541)
@ 24mA: 0 to
360Ω
@ 20mA: 0 to
450Ω
Safe-area load
(MTLx541S)
Current sink:
600Ω max.
Maximum voltage
source: 24V dc
Safe-area
circuit output resistance: > 1MΩ
Safe-area
circuit ripple
< 50µA
peak-to-peak
Hazardous-area
input
Signal range: 0
to 24mA (including over-range)
Transmitter
voltage: 16.5V at 20mA
Transfer
accuracy at 20°C
Better than
15µA
Temperature
drift
< 0.8µA/°C
Response time
Settles to
within 10% of final value within 50µs
Communications
supported
HART (terminals
1 & 2 only)
LED indicator
Green: power
indication
Maximum current
consumption (with 20mA signal)
51mA at 24V
Power
dissipation within unit (with 20mA signal)
MTLx541 0.7W @
24V dc
MTLx541S 1.0W @
24V dc
Safety
description
Terminals 2 to
1 and 3:
Uo=28V Io=93mA
Po=651mW Um = 253V rms or dc
Terminals 1 to
3:
Simple
apparatus ≤1.5V, ≤0.1A and ≤25mW; can be connected
without further
certification into any IS loop with an open-circuit
voltage <28V
Other related models for MTL4500 range as below
MTL4501-SR
MTL4504
MTL4510
MTL4510B
MTL4511
MTL4513
MTL4514D
MTL4514_B
MTL4516
MTL4516C
MTL4517
MTL4521
MTL4521L
MTL4523
MTL4523L
MTL4523R
MTL4523V-VL
MTL4524
MTL4524S
MTL4525
MTL4526
MTL4541
MTL4541A
MTL4541AS
MTL4541B
MTL4541P
MTL4541S
MTL4541T
MTL4544
MTL4544A
MTL4544AS
MTL4544B
MTL4544D
MTL4544S
MTL4546
MTL4546C
MTL4546S
MTL4546Y
MTL4549
MTL4549C
MTL4549Y
MTL4573
MTL4575
MTL4576-RTD
MTL4576-THC
MTL4581
MTL4582B
MTL4531
MTL4532
MTL4561
MTL4599
MTL4599N
If you have any other question about MTL4541, please feel free to contact me here!
Contact details
HONGKONG XIEYUAN TECH CO., LIMITED
Telephone:86-027-85508558
Mobile :86-15871691193(Whatapp&Wechat is available)
Skype:xyautomation
E-mail:sales1@hkxytech.com