Pepperl+Fuchs isolated barrier KFD2-SR2-EX.1.W.LB

  • Product Name:Pepperl+Fuchs isolated barrier KFD2-SR2-EX.1.W.LB
  • Product Number:KFD2-SR2-EX.1.W.LB
  • Brand:Pepperl Fuchs
  • Views:152
你添加了1件商品 查看购物车
简单介绍
Pepperl+Fuchs isolated barrier KFD2-SR2-EX.1.W.LB Pepperl+Fuchs isolated barrier KFD2-SR2-EX.1.W.LB Pepperl+Fuchs isolated barrier KFD2-SR2-EX.1.W.LB

Pepperl+Fuchs isolated barrier KFD2-SR2-EX.1.W.LB

的详细介绍

Pepperl+Fuchs isolated barrier KFD2-SR2-EX.1.W.LB



Switch Amplifier KFD2-SR2-Ex1.W.LB

Pepperl+Fuchs isolated barrier KFD2-SR2-EX.1.W.LB

Features
• 1-channel isolated barrier
• 24 V DC supply (Power Rail)
• Dry contact or NAMUR inputs
• Usable as signal splitter (1 input and 2 outputs)
• Relay contact output
• Fault relay contact output
• Line fault detection (LFD)
• Reversible mode of operation
• Up to SIL 2 acc. to IEC 61508/IEC 61511

Pepperl+Fuchs isolated barrier KFD2-SR2-EX.1.W.LB

Function
This isolated barrier KFD2-SR2-Ex1.W.LB is used for intrinsic safety applications. It transfers digital signals (NAMUR sensors/mechanical
contacts) from a hazardous area to a safe area. The proximity sensor or switch controls a form C changeover relay contact for the safe area load. The normal output state can be reversed using switch S1. Switch S2 allows output II to be switched between a signal output or an error message
output. Switch S3 is used to enable or disable line fault detection of the field circuit. During an error condition, the relays revert to their deenergized
state and the LEDs indicate the fault according to NAMUR NE44. A unique collective error messaging feature is available when used with the Power Rail system.Pepperl+Fuchs isolated barrier KFD2-SR2-EX.1.W.LB


General specifications
Signal type Digital Input
Functional safety related parameters
Safety Integrity Level (SIL) SIL 2
Supply
Connection Power Rail or terminals 14+, 15-
Rated voltage Ur 20 ... 30 V DC
Ripple ≤ 10 %
Rated current Ir ≤ 50 mA
Power dissipation 1 W
Power consumption < 1.3 W
Input
Connection side field side
Connection terminals 1+, 2+, 3-
Rated values acc. to EN 60947-5-6 (NAMUR)
Open circuit voltage/short-circuit current approx. 8 V DC / approx. 8 mA
Switching point/switching hysteresis 1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detection breakage I ≤ 0.1 mA , short-circuit I > 6 mA
Pulse/Pause ratio ≥ 20 ms / ≥ 20 ms
Output
Connection side control side
Connection output I: terminals 7, 8, 9 ; output II: terminals 10, 11, 12
Output I signal ; relay
Output II signal or error message ; relay
Contact loading 253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load
Minimum switch current 2 mA / 24 V DC
Energized/De-energized delay approx. 20 ms / approx. 20 ms
Mechanical life 107 switching cycles

Pepperl+Fuchs isolated barrier KFD2-SR2-EX.1.W.LB


Detailed models;

P+F KCD2-SCD-1
P+F KCD2-SCD-EX1
P+F KCD2-SR-EX1.LB
P+F KCD2-SR-EX2
P+F KCD2-STC-1
P+F KCD2-STC-EX1
P+F KCD2-STC-EX1.2O
P+F KCD2-UT2-EX1
P+F KFA6-SR2-Ex1.W
P+F KFD0-SD2-Ex1.1045
P+F KFD2-CD2-EX1
P+F KFD2-CRG2-EX1.D
P+F KFD2-DWB-1.D
P+F KFD2-EB2
P+F KFD2-GU-1
P+F KFD2-GUT-Ex1.D
P+F KFD2-SCD2-EX2.LK
P+F KFD2-SH-EX1.T.OP
P+F KFD2-SOT2-Ex2
P+F KFD2-SR2-Ex1.W.LB
P+F KFD2-SR2-Ex2.W
P+F KFD2-ST2-Ex2
P+F KFD2-STC4-1
P+F KFD2-STC4-EX2 
P+F KFD2-STC4-Ex2
P+F KFD2-UT2-1
P+F KFD2-UT2-2
P+F KFD2-UT2-EX1
P+F KFD2-UT2-Ex2
P+F KFD2-VR4-EX1.26

 

Copy right © 2018 Power by www.yi-z.cn Management Portal
Contact Person: Jessica Yu;  Tel: 86-027-85508558  Fax: +86 027-85309780
Mobile: 86-15871691193 (Whatsapp & Telegram)  Email: sales1@hkxytech.com; Jackie@hkxytech.com   Skype: Jackie@hkxytech.com

link: www.isolatorbarrier.ltd