Pepperl Fuchs HART Multiplexer Slave KFD0-HMS-16
Pepperl Fuchs HART Multiplexer Slave KFD0-HMS-16
Pepperl Fuchs HART Multiplexer Slave KFD0-HMS-16
Pepperl Fuchs HART Multiplexer Slave KFD0-HMS-16
Feature
16-channel
No external power required
HART field device input (revision 5 to 7)
Used with HART Multiplexer Master KFD2-HMM-16
Up to SIL 3 acc. to IEC/EN 61508
Pepperl Fuchs HART Multiplexer Slave KFD0-HMS-16
Function
This HART Multiplexer Slave operates up to 16 analog field instruments. It can be operated only with the HART Multiplexer Master KFD2-HMM-16
and is powered by the master across a 14- pin flat cable connection.
Up to 15 slaves can be connected to the master.
The slave address is set with a 16- position rotary switch (addresses 1 ... 16). If only one slave is connected to the master, then the slave address
should be 1. If multiple slaves are connected, slaves must be assigned addresses in ascending order.
The analog signals are fed into the slave by means of a 26-pin flat cable. Sixteen leads are reserved for the HART signal of the analog
measurement circuits. The remaining 10 leads are assigned to ground.
Pepperl Fuchs HART Multiplexer Slave KFD0-HMS-16
Assembly

Pepperl Fuchs HART Multiplexer Slave KFD0-HMS-16