MTL safety barriers MTL5032 Pulse Isolator
日期:2025-05-01 19:41
浏览次数:71
摘要:MTL safety barriers MTL5032 Pulse Isolator
MTL safety barriers MTL5032 Pulse Isolator
MTL safety barriers MTL5032 Pulse Isolator
MTL safety barriers MTL5032 Pulse Isolator
MTL safety barriers MTL5032 Pulse Isolator
MTL safety barriers MTL5032 Pulse Isolator
Feature
The MTL5032 isolates pulses from a switch, proximity detector, current pulse transmitter or voltage pulse transmitter located in a hazardous area.
MTL safety barriers MTL5032 Pulse Isolator
Specification
One
Location of switch
Zone 0, IIC, T6 hazardous area
Div. 1, Group A hazardous location
Location of proximity detector or transmitter
Zone 0, IIC, T4–6 hazardous area if suitably certified
Div. 1, Group A hazardous location
Safe-area output
Maximum off-state values: V = 35V, I = 10µA
Maximum on-state current: 50mA
Voltage drop: [1 + (0.1 x current in mA)] V
Output off if supply fails
Hazardous-area input
Switch: output-on (off) if switch closed (open)
Proximity detector: meets NAMUR and DIN 19234 standards
Pulse (I): Supply 16.5V dc at 20mA,
Short-circuit current 24mA
Output on (off) >8.9mA (<6.8mA)
Switching hysteresis: 0.5mA typical
Pulse (V): Input impedance >10kΩ
Switching point voltage (Vsp): 3, 6 or 12V
(selectable)
Output on (off) if input >1.2 x Vsp (<0.8 x Vsp)
Switching hysteresis: 0.11 x Vsp typical
Pulse width
High: 10µs minimum
Low: 10µs minimum
Frequency range
0 to 50kHz
MTL safety barriers MTL5032 Pulse Isolator

MTL safety barriers MTL5032 Pulse Isolator