REPEATER POWER SUPPLY 2-channel, 4/20mA, HART庐, 2- or 3-wire transmitters The MTL4544B provides
fully-floating dc supplies for energising two conventional 2- or 3-wire 4/20mA
or HART transmitters located in a hazardous area, and repeats the current in
other circuits to drive two safe-area loads. For HART transmitters, the unit
allows bi-directional transmission of digital communication signals
superimposed on the 4/20mA signal so that the transmitter can be interrogated
either from the operator station or by a hand-held communicator.
SPECIFICATION
MTL4544B MTL4044 replacement original isolated barrier
See also common
specification
Number of
channels
Two
Location of
transmitter
Zone 0, IIC,
T4-6, hazardous area if suitably certified
Div 1, Group A,
hazardous location
Safe-area
output
Signal range: 4
to 20mA
Under/over-range:
0 to 24mA
Safe-area load
resistance: 0 to 360Ω @ 24mA
0 to 450Ω @
20mA
Safe-area
circuit output resistance: > 1MΩ
Safe-area
circuit ripple
< 50µA
peak-to-peak
Hazardous-area
input
Signal range: 0
to 24mA (including over-range)
Transmitter
voltage: 16.5V at 20mA
Transfer
accuracy at 20°C
Better than
20µA
Temperature
drift
< 0.8µA/°C
Response time
Settles to
within 10% of final value within 50µs
Communications
supported
HART®
(terminals 1 & 2 and 4 & 5 only
LED indicator
Green: power
indication
Maximum current
consumption (with 20mA signals)
96mA at 24V dc
Power
dissipation within unit (with 20mA signals)
1.4W at 24V dc
Safety
description (each channel)
Terminals 2 to
1 and 3, and 5 to 4 and 6:
Vo=28V Io=93mA
Po=651mW Um = 253V rms or dc
Terminals 1 to
3 and 4 to 6:
Simple
apparatus ≤1.5V, ≤0.1A and ≤25mW; can be connected
without further
certification into any IS loop with an open-circuit
voltage <28V
Other related models for MTL4500 range as below
MTL4544B MTL4044 replacement original isolated barrier
MTL4501-SR
MTL4504
MTL4510
MTL4510B
MTL4511
MTL4513
MTL4514D
MTL4514_B
MTL4516
MTL4516C
MTL4517
MTL4521
MTL4521L
MTL4523
MTL4523L
MTL4523R
MTL4523V-VL
MTL4524
MTL4524S
MTL4525
MTL4526
MTL4541
MTL4541A
MTL4541AS
MTL4541B
MTL4541P
MTL4541S
MTL4541T
MTL4544
MTL4544A
MTL4544AS
MTL4544B
MTL4544D
MTL4544S
MTL4546
MTL4546C
MTL4546S
MTL4546Y
MTL4549
MTL4549C
MTL4549Y
MTL4573
MTL4575
MTL4576-RTD
MTL4576-THC
MTL4581
MTL4582B
MTL4531
MTL4532
MTL4561
MTL4599
MTL4599N
MTL4544B MTL4044 replacement original isolated barrier
Contact details
HONGKONG XIEYUAN TECH CO., LIMITED
Telephone:86-027-85508558
Mobile :86-15871691193(Whatapp&Wechat
is available)
Skype:xyautomation
E-mail:sales1@hkxytech.com