	The MTL4504 enables a safe–area load to be controlled, through a
relay, by a proximity detector or switch located in a hazardous area. Line
faults are signalled through a separate relay and indicated on the top of
the module. MTBF information for the LFD relay is available from Eaton
to allow the failure rate for the LFD relay to be calculated when used
in the critical path with the output relay for safety critical applications.
Switches are provided to select phase reversal and to enable the line
fault detection.
 
MTL Safety Barriers Crouse-Hinds Switch/ Proximity Detector Interface MTL4504
	
 
	Number of channels
	One
	Location of switch
	Zone 0, IIC, T6 hazardous area Div.1, Group A, hazardous location
	Location of proximity detector
	Zone 0, IIC, T4–6 hazardous area, if suitably certified Div.1, Group A, hazardous location
	Hazardous–area inputs
	Inputs conforming to BS EN60947–5–6:2001 standards for proximity detectors (NAMUR)
	Voltage applied to sensor
	7 to 9V dc from 1kΩ ±10%
	Input/output characteristics
	Normal phase
	Outputs closed if input > 2.1mA (< 2kΩ in input circuit) Outputs open if input < 1.2mA (> 10kΩ in input circuit)
	Hysteresis: 200µA (650Ω) nominal
MTL Safety Barriers Crouse-Hinds Switch/ Proximity Detector Interface MTL4504
	
	Line fault detection (LFD) (when selected)
User-selectable via switches on the side of the unit. Line faults are 
indicated by an LED. Line fault relay is de-energised and channel 
output relay de-energised if input line-fault detected
Open-circuit alarm on if Iin < 50µA
Open-circuit alarm off if Iin > 250µA
Short-circuit alarm on if Rin < 100Ω
Short-circuit alarm off if Rin > 360Ω
Note: Resistors must be fitted when using the LFD facility with a contact input
500Ω to 1kΩ in series with switch
20kΩ to 25kΩ in parallel with switch 
MTL Safety Barriers Crouse-Hinds Switch/ Proximity Detector Interface MTL4504
Relay characteristics
	 
	 
						 
					 
						MTL4504 
					 
						Response time: 
					 
						10ms maximum 
					 
						Contact rating (Safe Area): 
					 
						10W, 0.5A, 
					 
						35V dc 
					 
						Contact rating (Zone 2): 
					 
						10W, 0.5A, 
					 
						35V dc 
					
		
			