The MTL4504 enables a safe–area load to be controlled, through a relay, by a proximity detector or switch located in a hazardous area. Line faults are signalled through a separate relay and indicated on the top of the module. MTBF information for the LFD relay is available from Eaton to allow the failure rate for the LFD relay to be calculated when used in the critical path with the output relay for safety critical applications. Switches are provided to select phase reversal and to enable the line fault detection.

MTL Safety Barriers Crouse-Hinds Switch/ Proximity Detector Interface MTL4504


Number of channels

One

Location of switch

Zone 0, IIC, T6 hazardous area Div.1, Group A, hazardous location

Location of proximity detector

Zone 0, IIC, T46 hazardous area, if suitably certified Div.1, Group A, hazardous location

Hazardousarea inputs

Inputs conforming to BS EN6094756:2001 standards for proximity detectors (NAMUR)

Voltage applied to sensor

7 to 9V dc from 1kΩ ±10%

Input/output characteristics

Normal phase

Outputs closed if input > 2.1mA (< 2kin input circuit) Outputs open if input < 1.2mA (> 10kin input circuit)

Hysteresis: 200µA (650) nominal

MTL Safety Barriers Crouse-Hinds Switch/ Proximity Detector Interface MTL4504


Line fault detection (LFD) (when selected)
User-selectable via switches on the side of the unit. Line faults are 
indicated by an LED. Line fault relay is de-energised and channel 
output relay de-energised if input line-fault detected
Open-circuit alarm on if Iin < 50µA
Open-circuit alarm off if Iin > 250µA
Short-circuit alarm on if Rin < 100Ω
Short-circuit alarm off if Rin > 360Ω
Note: Resistors must be fitted when using the LFD facility with a contact input
500Ω to 1kΩ in series with switch
20kΩ to 25kΩ in parallel with switch

MTL Safety Barriers Crouse-Hinds Switch/ Proximity Detector Interface MTL4504

Relay characteristics

MTL4504

Response time:

10ms maximum

Contact rating (Safe Area):

10W, 0.5A,

35V dc

Contact rating (Zone 2):

10W, 0.5A,

35V dc