MTL4510 – MTL5510 SWITCH/ PROXIMITY DETECTOR INTERFACE
4-channel, digital input
The MTLx510 enables four solid-state outputs in the safe area to be controlled by up to four switches or proximity detectors located in a hazardous area. Each pair of output transistors shares a common terminal and can switch +ve or –ve polarity signals. A range of module configurations is available (see Table 1) through the use of selector switches. When proximity detector modes are selected, LFD is enabled and the output switches to OFF if a line fault is detected.
MTL Safety Barriers Crouse-Hinds Switch/ Proximity Detector Interface MTL4510
Specification:
Number of channels
4, configured by switches
Location of switches
Zone 0, IIC, T6 hazardous area Div 1, Group A hazardous location
Location of proximity detectors
Zone 0, IIC, T4-6 hazardous area if suitably certified Div 1, Group A, hazardous location
Hazardous-area inputs
Inputs conforming to BS EN60947–5–6:2001 standards for proximity detectors (NAMUR)
Voltage applied to sensor
7 to 9V dc from 1kΩ ±10%
Input/output characteristics
Normal phase
Outputs closed if input > 2.1mA (< 2kΩ in input circuit)
Outputs open if input < 1.2mA (> 10kΩ in input circuit)
Hysteresis: 200µA (650Ω) nominal
Line fault detection (LFD) (when selected)
User-selectable via switches on the side of the unit. Open-circuit alarm on if Iin < 50µA
Open-circuit alarm off if Iin > 250µA
Short-circuit alarm on if Rin < 100Ω Short-circuit alarm off if Rin > 360Ω
Note: Resistors must be fitted when using the LFD facility with a contact input
500Ω to 1kΩ in series with switch
20kΩ to 25kΩ in parallel with switch
MTL Safety Barriers Crouse-Hinds Switch/ Proximity Detector Interface MTL4510
Mode options
MODE
o/p 1
o/p 2
o/p 3
o/p 4
i/p type
0
chA
chB
chC
chD
switch
1
chA rev.
chB
chC
chD
2
chA
chB rev.
chC
chD
3
chA
chB
chC rev.
chD
4
chA
chB
chC
chD rev.
5
chA rev.
chB
chC rev.
chD
6
chA
chB rev.
chC
chD rev.
7
chA rev.
chB rev.
chC rev.
chD rev.
8
chA
chB
chC
chD
prox. detector
+ LFD
9
chA rev.
chB
chC
chD
10
chA
chB rev.
chC
chD
11
chA
chB
chC rev.
chD
12
chA
chB
chC
chD rev.
13
chA rev.
chB
chC rev.
chD
14
chA
chB rev.
chC
chD rev.
15
chA rev.
chB rev.
chC rev.
chD rev.
MTL Safety Barriers Crouse-Hinds Switch/ Proximity Detector Interface MTL4510
Type
MTL4510 – MTL5510
MTL Safety Barriers Crouse-Hinds Switch/ Proximity Detector Interface MTL4510