Endress+Hauser iTEMP TMT82-BAA1EB1A1AAA1+E1 HART Temperature Transmitter
- Product Name:Endress+Hauser iTEMP TMT82-BAA1EB1A1AAA1+E1 HART Temperature Transmitter
- Product Number:TMT82-BAA1EB1A1AAA1+E1
- Brand:Endress+Hauser
- Views:0
-
Endress+Hauser iTEMP TMT82-BAA1EB1A1AAA1+E1 HART Temperature Transmitter
的详细介绍
Endress+Hauser iTEMP TMT82-BAA1EB1A1AAA1+E1
HART Temperature Transmitter


The Endress+Hauser iTEMP TMT82-BAA1EB1A1AAA1+E1 is a highly reliable, dual-channel temperature transmitter from the iTEMP series, designed for industrial processes requiring high availability . This versatile device converts universal sensor inputs (RTD, thermocouple, resistance, voltage) into stable 4-20 mA analog signals with HART® 7 communication . Featuring SIL 2/SC3 certification and smart sensor monitoring according to NAMUR NE 107, it increases process safety and uptime .
Order Code Interpretation: TMT82-BAA1EB1A1AAA1+E1
Based on Endress+Hauser's ordering structure for the iTEMP TMT82 series:
| Position | Code | Interpretation |
|---|---|---|
| Basic | TMT82 | iTEMP HART temperature transmitter |
| Approval | B | ATEX/IECEx Ex ia (intrinsic safety for hazardous areas) |
| Version | AA | Standard version |
| Input/Output | 1 | 2x universal inputs (RTD/TC/Ω/mV); 1x output 4-20mA HART |
| Connection | E | Screw terminals (or push-in terminals depending on version) |
| Housing | B | Head transmitter for DIN EN 50446 terminal head mounting |
| Options | 1A1AAA1 | Standard configuration with specific hardware/software settings |
| +E1 | E1 | Additional option (typically HART communication package) |
Key Features & Benefits
-
Dual Universal Inputs: Accepts 2 independent sensors: RTD (Pt100, Ni100, Cu50), thermocouple (K, J, N, S, R, etc.), resistance (Ω), and voltage (mV) signals .
-
SIL 2/SC3 Certified: Certified for functional safety applications according to IEC 61508:2010, suitable for use in safety instrumented systems .
-
High Accuracy: Pt100 accuracy ≤ 0.1 K over -50 to 200°C range; transmitter-sensor matching for highest measurement precision .
-
Smart Sensor Monitoring: Built-in diagnostics according to NAMUR NE 107 with sensor and hardware failure detection .
-
Tool-Free Wiring: Push-in terminal technology enables fast, tool-free installation (on select versions) .
-
Versatile Mounting Options: Fits in terminal head form B (DIN EN 50446), DIN rail, or field housing with IP68 protection class .
-
HART® 7 Communication: Advanced digital communication with secure HART commands for SIL mode operation .
-
Marine Approvals: DNV GL certified for use in marine applications .
-
Galvanic Isolation: 2 kV isolation between input, output, and power supply for enhanced safety .
Technical Specifications
| Parameter | Specification |
|---|---|
| Manufacturer | Endress+Hauser |
| Product Series | iTEMP TMT82 |
| Measuring Principle | Head transmitter (temperature) |
| Inputs | 2 x universal: RTD, TC, Ω, mV |
| RTD Types | Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Cu50, Cu100 |
| Thermocouple Types | K, J, N, S, R, E, T, B, C, D, L |
| Output | 1 x analog 4-20 mA / HART |
| Auxiliary Power Supply | 11-42 V DC (head transmitter), 12-42 V DC (DIN rail) |
| Accuracy (Pt100) | ≤ 0.1 K (-50 to 200°C) |
| Long-term Stability | ≤ 0.05°C/year or 0.02% of span/year |
| Galvanic Isolation | Yes, 2 kV |
| Housing | Head transmitter for terminal head form B (DIN EN 50446) |
| Dimensions | Head transmitter: 33 x 33 x 17.5 mm (1.3 x 1.3 x 0.69 in) |
| Ambient Temperature | -40 to +85°C (-40 to +185°F) |
| Ingress Protection | Up to IP68 (depending on housing) |
| SIL Certification | SIL 2 / SC3 according to IEC 61508:2010 |
| Hazardous Area Approvals | ATEX, IECEx, FM, CSA, NEPSI, INMETRO, EAC |
| Marine Approvals | DNV GL, ABS, LR, BV |
| Configuration | HART, FieldCare, DeviceCare, Field Xpert |
| Communication | HART® 7 protocol |
Installation Options
The TMT82 offers three mounting configurations :
-
Head Transmitter (this model): Directly mounted in terminal head form B (DIN EN 50446) for integration with existing thermowell assemblies.
-
DIN Rail Transmitter: Mounts on 35mm DIN rail (17.5mm width) for control cabinet installation.
-
Field Housing: IP66/67 enclosure for direct field mounting, separate from process connection.
Optional Display: TID10 pluggable display can be added for local measured value indication and configuration .

TMT82
Q&A
Q1: What types of sensors can I connect to the TMT82-BAA1EB1A1AAA1+E1?
A: The TMT82 features 2 universal inputs that accept a wide range of sensors . For RTDs, it supports Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Cu50, and Cu100. For thermocouples, it supports Types K, J, N, S, R, E, T, B, C, D, and L. It also accepts direct resistance (Ω) and voltage (mV) inputs. The two channels are independent but must use the same measurement unit (e.g., both °C) .
Q2: What is the accuracy of the TMT82, and is it certified for safety applications?
A: For Pt100 sensors over -50 to 200°C, the TMT82 delivers ≤ 0.1 K accuracy . It is certified for SIL 2 / SC3 according to IEC 61508:2010, making it suitable for use in safety instrumented systems . The device also features sensor and hardware failure detection with diagnostics according to NAMUR NE 107.
Q3: What mounting options does the TMT82 offer, and how easy is it to install?
A: This specific version (B housing) is a head transmitter designed for mounting in terminal heads per DIN EN 50446 . Alternative versions are available for DIN rail mounting (17.5 mm width) or field housing. Installation is simplified by push-in terminal technology for tool-free wiring on select versions . The HART protocol enables easy configuration using FieldCare, DeviceCare, or handheld communicators .