Pepperl+Fuchs FC-GPCS-RIO16-PF | Termination Board for Honeywell Safety Manager | 16-Channel

  • Product Name:Pepperl+Fuchs FC-GPCS-RIO16-PF | Termination Board for Honeywell Safety Manager | 16-Channel
  • Product Number:FC-GPCS-RIO16-PF
  • Brand:Pepperl Fuchs
  • Views:13
你添加了1件商品 查看购物车
简单介绍
Key Benefits at a Glance System board for Honeywell Safety Manager For 32-channel universal I/O card RUSIO-3224 For 16 modules Recommended modules: HiC2025(A)(ES) (AI), HiC2031(ES) (AO), HiC2441 (UIO), HiC2831R2 (DI), HiC2853R2 (DI), HiC2871 (DO), HiC5861 (DO), HiC5863 (DO) Recommended system cable: CAB-HON-**-S37C32-MX-01000 24 V DC supply Hazardous area: pluggable screw terminals, blue N

Pepperl+Fuchs FC-GPCS-RIO16-PF | Termination Board for Honeywell Safety Manager | 16-Channel

的详细介绍


Pepperl+Fuchs FC-GPCS-RIO16-PF |
 Termination Board for Honeywell Safety Manager | 16-Channel


Meta Description:

Pepperl+Fuchs FC-GPCS-RIO16-PF termination board. Designed for Honeywell Safety Manager and Universal I/O cards, this 16-channel board supports multiple signal types with 24V DC supply and blue screw terminals for hazardous areas.

 Pepperl+Fuchs FC-GPCS-RIO16-PF Termination Board (Part No.: FC-GPCS-RIO16-PF / 232114)

The Pepperl+Fuchs FC-GPCS-RIO16-PF is a high-density termination board engineered to provide a seamless interface between field devices in hazardous areas and Honeywell control and safety systems . Designed specifically for the Honeywell Safety Manager and Universal I/O platforms, this system board accommodates up to 16 isolated barrier modules and connects directly to 32-channel universal I/O cards such as the RUSIO-3224 . This makes it an essential component for intrinsic safety (IS) applications in process automation.


Key Features and Product Highlights

  • Designed for Honeywell Systems: Specifically configured for seamless integration with Honeywell Safety Manager and Universal Process I/O systems, connecting directly to 32-channel cards like the RUSIO-3224 .

  • Supports Universal I/O Technology: Fully compatible with the HiC2441 Universal Barrier, which automatically adapts to any signal type (AI, AO, DI, DO) without configuration, extending Honeywell's Universal Channel Technology to the field .

  • 16-Channel Capacity: Supports up to 16 single-channel isolated barriers, providing a high-density I/O solution for space-constrained cabinets while maintaining signal integrity .

  • Integrated Power Distribution and Redundancy: Features a 24V DC supply with reverse polarity protection. The supply to the modules is decoupled, monitored, and fused, and it supports redundant power connections for increased system availability .

  • Comprehensive Diagnostics: Equipped with a fault indication relay output (volt-free contact) and LED status indicators on the board.

    • Supply LEDs (Green): Two LEDs monitor the status of power supply I and power supply II.

    • Fault LED (Red): Provides a visual alert for power supply faults .

  • Hazardous Area Interface: The field side utilizes blue pluggable screw terminals for connecting field devices located in hazardous areas, ensuring secure and reliable terminations with safe electrical isolation up to 375V peak .

  • Wide Module Compatibility: Supports a comprehensive range of Pepperl+Fuchs modules including HiC2025(A) (AI), HiC2031 (AO), HiC2441 (UIO), HiC2831R2 (DI), HiC2853R2 (DI), HiC2871 (DO), HiC5861 (DO), and HiC5863 (DO) .

Technical Specifications

Parameter Specification
Manufacturer Pepperl+Fuchs
Part Number FC-GPCS-RIO16-PF
Alternate Part Number 232114 
Product Type Termination Board / System Board
System Compatibility Honeywell Safety Manager, Universal I/O (for RUSIO-3224 card) 
Number of Module Slots 16 
Signal Types Supported AI, AO, DI, DO, Universal (via HiC2441) 
Recommended System Cable CAB-HON-**-S37C32-MX-01000 
Supply Connection TB3: terminals 2, 4 (+); 1, 3 (-) 
Nominal Voltage 24 V DC 
Fusing 4 A per 16 modules 
Fault Indication Output Volt-free relay contact, TB4: terminals 1, 2 (30 V DC, 1 A) 
Display Elements LEDs for Supply 1 (green), Supply 2 (green), and Error Status (red) 
Field Side Connection Pluggable screw terminals (blue), for hazardous area 
Control Side Connection 37-pin Sub-D connector (male) 
Supply/Fault Connection Pluggable screw terminals (black) 
Wire Size (Field) 0.25 ... 2.5 mm² (24 ... 12 AWG) 
Ambient Temperature -20 ... 60 °C (-4 ... 140 °F) 
Protection Rating IP20 
Mounting 35 mm DIN mounting rail acc. to EN 60715 
Dimensions (W x H x D) 273 x 155 x 153 mm (10.7 x 6.1 x 6.0 inch) 
Approvals / Certificates ATEX, IECEx, UL (for associated IS applications) 

Applications

  • Honeywell DCS and Safety Systems: Ideal for integrating field sensors and actuators from hazardous areas into Honeywell Safety Manager and Experion PKS platforms .

  • Universal Marshalling Solutions: Serves as the foundation for the HiC2441 Universal Barrier, enabling "one device fits all" signal types and simplifying cabinet design for Honeywell's LEAP project methodology .

  • Intrinsic Safety Interfaces: Functions as the backbone for mounting isolated barriers, ensuring safe and organized wiring for intrinsic safety circuits in chemical, petrochemical, and pharmaceutical plants .

  • High-Density Cabinet Design: The 16-channel capacity optimizes I/O density within control panels, reducing overall cabinet footprint and wiring complexity.

  • Greenfield and Brownfield Projects: Equally suited for new DCS installations or for upgrading existing analog marshalling cabinets to modern, high-density digital I/O architectures.



 

Copy right © 2018 Power by www.yi-z.cn Management Portal
Contact Person: Jessica Yu;  Tel: 86-027-85508558  Fax: +86 027-85309780
Mobile: 86-15871691193 (Whatsapp & Telegram)  Email: sales1@hkxytech.com; Jackie@hkxytech.com   Skype: Jackie@hkxytech.com

link: www.isolatorbarrier.ltd