AIP831 Operation Keyboard for Eight-loop Simultaneous Operation
- Product Name:AIP831 Operation Keyboard for Eight-loop Simultaneous Operation
- Product Number:AIP831
- Brand:Yokogawa
- Views:240
-
AIP831 Operation Keyboard for Eight-loop Simultaneous Operation
的详细介绍Yokogawa AIP831 Operation Keyboard for Eight-loop Simultaneous Operation
Model AIP831
Operation Keyboard for Single-loop Operation
It contains an independent USB speaker (a sound function) other than buzzing alarms (buzzer sounds).
An AIP830 Keyboard can be used per one Desktop Type HIS.
HARDWARE SPECICATIONS
Yokogawa AIP831 Operation Keyboard for Single-loop Operation
For installation specifications and environmental conditions, which are common to the systems, refer to “System
Overview” (GS 33K01A10-50E, GS 33K01A20-50E).
• Type: Flat keyboard (Sound Function: USB Speaker)
• PC Interface:
Interface Connector: USB A type x 2 (*1)
Conformable USB standard
Operation Keyboard Function : USB 2.0 (Full-speed, Bus-powered)
Sound Function : USB 1.1 (Full-speed, Bus-powered)
• Input Voltage: 5 V±5 % (Supplied from USB Port of PC)
• Maximum Consumption Current: 1 A
• Weight: 2.0kg (Without VESA Bracket), 2.5 kg (With VESA Braceket) (*2)
• Chassis Color: Black (Equivalent to Munsell No. N1.5)
• AIP831 belongs to IEC 61010-1 installation category Class I
(A device not directly connected with the main power supply).
• Operating Environment
Ambient temperature:
5 to 40 °C (for normal operaiton)
-20 to 60 °C (in storage and transportation)
Ambient humidity:
20 to 80 %RH (Non-condensing)
*1: Both connectors must always be connected directly to a PC.
*2: AIP830 with VESA Bracket must be mounted where it holds at least 10 kg of weight.
REGULATORY COMPLIANCE
Yokogawa AIP831 Operation Keyboard for Single-loop Operation
For the detailed information of the following standards, refer to “System Overview” (GS 33K01A10-50E,GS 33K01A20-50E).
Safety Standards
[CSA] (*1)
[CE Marking] (*2)
EMC Conformity Standards
[CE Marking] (*2) (*5)
[C-Tick Marking] (*3)
[KC Marking] (*4)
*1: AIP831 complies to CSA only when CSA mark is indicated on the PC which connects with AIP830.
*2: AIP831 complies to CE Marking only when CE mark is indicated on the PC which connects with AIP830.
*3: AIP831 complies to C-tick marking ionly when it is indicated on the PC which connects with AIP830.
*4: AIP831 complies to KC Marking only when KC mark is indicated on the PC which connects with AIP830.
*5: EN 61000-3-2 and EN 61000-3-3 in CE Marking are out of scope for AIP830.