AAI143-S53

  • Product Name:AAI143-S53
  • Product Number:AAI143-S53
  • Brand:Yokogawa
  • Views:201
你添加了1件商品 查看购物车
简单介绍
AAI143-S53,AAI143-S53

AAI143-S53

的详细介绍

Yokogawa Analog Input Module AAI143-S53

Manufacturer: Yokogawa Electric Corporation

Control System: CENTUM VP

STANDARD SPECIFICATIONS

Current Input Modules (Isolated)
This module inputs 4 to 20 mA.
It can be used in dual redundant configuration.

Yokogawa Analog Input Module AAI143-S53

Items

Specifications

Model

AAI143 (*1)

Number of input channels

16,  isolated

Input signal

4 to 20 mA

Allowable input current

24 mA

Withstanding voltage

Between input and system: 1500 V AC For 1 minute (*4)

Input resistance

Power ON

270 Ω (20 mA) to 350 Ω (4 mA) (*2)

Power OFF

500 kΩ or more

Accuracy

±16 μA

Data update period

10 ms

Transmitter power supply

19.0 V or more (at 20 mA) 25.5 V or less (at 0 mA) (output current limit: 25 mA) (*5)

Setting of 2-wire or 4-wire transmitter

For each channel by setting pin

Drift due to ambient temperature change

±16 μA/10˚C

Maximum current consumption

230 mA (5 V DC) , 540 mA (24 V DC)

Weight

0.3 kg

External communication

Pressure clamp terminal, MIL connector cable, Dedicated cable (KS1)

HART communication (*3)

Available

 

 

 

*1: This module Yokogawa Analog Input Module AAI143-HE3 does not allow a Zener barrier to be connected. If the module is to be used in intrinsically safe applications, use an isolation barrier.

*2: Viewed from the terminals, module input resistance is, depending on the current flowing:

250 Ω + voltage drop (0.4 V maximum) in the input protection circuit/current value

*3: When installing the module Yokogawa Analog Input Module AAI143-HE3 with HART function to a remote node, the firmware of EB401 must be Rev 2 or later.For HART function specifications, refer to “HART Communication Package (for A□I□□□-H) (GS 33Q03L70-31E).”

*4: The withstanding voltage for using the dedicated cable is 500 V AC (between the input signal and the system).The withstanding voltage for using MIL connector cable depends on the electrical specifications of its cable.

*5: This voltage is developed between connecting terminals for this Yokogawa Analog Input Module AAI143-S53 module’s 2-wire transmitter. When calculating if transmitter minimum operating voltage requirement will be satisfied, remember to allow for voltage drop in external wiring.

 

MODELS AND SUFFIX CODES

Yokogawa Analog Input ModuleAAI143-S53

 

 

Description

Model

AAI143

Analog Input Module (4 to 20 mA, 16-channel, Isolated)

Suffix Codes

-S

Standard type

-H

With digital communication (HART protocol)

5

With no explosion protection

E

With explosion protection

0

Basic type

3

With ISA Standard G3 option and temperature (-20 to 70 °C) option

Option Codes

/K4A00

With KS Cable Interface Adapter (For connecting AEA4D Terminal Board) [Model: ATK4A-00]

/A4S00

With Pressure Clamp Terminal Block [Model: ATA4S-00]

/A4S10

With Pressure Clamp Terminal Block (surge absorber) [Model: ATA4S-10]

/A4D00

With Dual Pressure Clamp Terminal Block [Model: ATA4D-00]

/A4D10

With Dual Pressure Clamp Terminal Block (surge absorber) [Model: ATA4D-10]

/CCC01

With Connector Cover for MIL Cable [Model: ACCC01]

 

YOKOGAWA AAI143-S53 Analog Input Module

Selected Model

AAI143-S50/K4A00, AAI143-S50/A4S00, AAI143-S50/A4S10, AAI143-S50/A4D00, AAI143-S50/A4D10, AAI143-S50/CCC01,

AAI143-S53/K4A00, AAI143-S53/A4S00, AAI143-S53/A4S10, AAI143-S53/A4D00, AAI143-S53/A4D10, AAI143-S53/CCC01,

AAI143-SE0/K4A00, AAI143-SE0/A4S00, AAI143-SE0/A4S10, AAI143-SE0/A4D00, AAI143-SE0/A4D10, AAI143-SE0/CCC01,

AAI143-SE3/K4A00, AAI143-SE3/A4S00, AAI143-SE3/A4S10, AAI143-SE3/A4D00, AAI143-S53/A4D10, AAI143-S53/CCC01,

AAI143-H50/K4A00, AAI143-H50/A4S00, AAI143-H50/A4S10, AAI143-H50/A4D00, AAI143-h50/A4D10, AAI143-H50/CCC01,

AAI143-H53/K4A00, AAI143-H53/A4S00, AAI143-H53/A4S10, AAI143-H53/A4D00, AAI143-h53/A4D10, AAI143-H53/CCC01,  AAI143-HE0/K4A00, AAI143-HE0/A4S00, AAI143-HE0/A4S10, AAI143-HE0/A4D00, AAI143-HE0/A4D10, AAI143-HE0/CCC01,

AAI143-HE3/K4A00, AAI143-HE3/A4S00, AAI143-HE3/A4S10, AAI143-HE3/A4D00, AAI143-HE3/A4D10, AAI143-HE3/CCC01

Email address: Jackie@hkxytech.com sale1@hkxytech.com.
WhatSapp:+86 15717178751     +86 15871691193
Skype: Jackie@hkxytech.com

 

 

Copy right © 2018 Power by www.yi-z.cn Management Portal
Contact Person: Jessica Yu;  Tel: 86-027-85508558  Fax: +86 027-85309780
Mobile: 86-15871691193 (Whatsapp & Telegram)  Email: sales1@hkxytech.com; Jackie@hkxytech.com   Skype: Jackie@hkxytech.com

link: www.isolatorbarrier.ltd