Description
The MTL5061 is a loop-powered two-channel interface for use with conventional fire and smoke detectors located in hazardous areas. In operation, the triggering of a detector causes a orresponding change in the safe-area circuit. The unit has reverse input polarity protection, while ‘non-fail’ earth fault detection on either line can be provided by connecting an earth leakage detector to terminals 3 or 6.
MTL Safety Barriers Fire Smoke Detector Interface MTL5061
Specification
Number of channels
Two
Location of detectors
Zone 0, IIC, T4–6 hazardous area if suitably certified
Div. 1, Group A hazardous location
Current range
1 to 40mA, nominal
Integral input polarity protection
Input circuit protected against reverse polarity
‘No-fail‘ earth fault protection (optional)
Enabled by connecting terminals 3 and 6 to the MTL4220 earth
leakage detector. If a fault on either line of each channel is
proclaimed: unit continues working.
Note:1. The earth leakage detector introduces a 100µA, 1Hz ripple to the
field circuit.
Minimum output voltage Vout at 20ºC
whichever is the lower of:
Vin – (0.38 x current in mA) – 2V or
21V – (0.35 x current in mA)
Response time to step input
Settles to within 500µA of final value within 30ms
Hazardous-area output
Maximum output voltage 28V from 300Ω
Transfer accuracy at 20°C
Better than 400µA
Temperature drift
<10µA/°C (–20 to 60°C)
Loop supply voltage
6 to 35V dc
Quiescent safe-area current at 20°C
(hazardous-area terminals open-circuit)
<400µA/ channel, Vin = 24V dc
Maximum power dissipation within unit
0.7W at 24V with 40mA signal (each channel)
1.2W at 35V with 40mA signal (each channel)
Safety description
28V, 300Ω, 93mA; Um = 250V rms or dc
MTL Safety Barriers Fire Smoke Detector Interface MTL5061