MTL safety barriers MTL 5511 Switch/ Proximity Detector Interface

  • Product Name:MTL safety barriers MTL 5511 Switch/ Proximity Detector Interface
  • Product Number:MTL 5511
  • Brand:MTL
  • Views:53
你添加了1件商品 查看购物车
简单介绍
MTL safety barriers MTL 5511 Switch/ Proximity Detector Interface MTL safety barriers MTL 5511 Switch/ Proximity Detector Interface MTL safety barriers MTL 5511 Switch/ Proximity Detector Interface

MTL safety barriers MTL 5511 Switch/ Proximity Detector Interface

的详细介绍

MTL safety barriers MTL 5511 Switch/ Proximity Detector Interface


MTL safety barriers MTL 5511 Switch/ Proximity Detector Interface

MTL safety barriers MTL 5511 Switch/ Proximity Detector Interface


Feature

The MTLx511 enables a safe-area load to be controlled by a switch or proximity detector located in a hazardous-area. When selected, open or short circuit conditions in the field wiring are detected by the linefault-detect (LFD) facility and also indicated on the top of the module. Phase reversal for the channel is selected by a switch on the side of the module and output is provided by changeover relay contacts.

MTL safety barriers MTL 5511 Switch/ Proximity Detector Interface

Specification

Number of channels
One
Location of switches
Zone 0, IIC, T6 hazardous area
Div. 1, Group A hazardous location
Location of proximity detector
Zone 0, IIC, T4–6 hazardous area if suitably certified
Div. 1, Group A hazardous location
Hazardous-area inputs
Inputs conforming to BS EN60947–5–6:2001 standards for
proximity detectors (NAMUR)
Voltage applied to sensor
7 to 9V dc from 1kΩ ±10%
Input/output characteristics
Normal phase
Outputs closed if input > 2.1mA (< 2kΩ in input circuit)
Outputs open if input < 1.2mA (> 10kΩ in input circuit)
Hysteresis: 200µA (650Ω) nominal
Line fault detection (LFD) (when selected)
User-selectable via switches on the side of the unit. A line fault is
indicated by an LED. The channel output relay is de-energised if an
input line fault is detected.
Open-circuit alarm on if Iin < 50µA
Open-circuit alarm off if Iin > 250µA
Short-circuit alarm on if Rin < 100Ω
Short-circuit alarm off if Rin > 360Ω
Note: Resistors must be fitted when using the LFD facility with a contact input
500Ω to 1kΩ in series with switch
20kΩ to 25kΩ in parallel with switch
Safe-area output
Single pole relay with changeover contacts
Note: reactive loads must be adequately suppressed

MTL safety barriers MTL 5511 Switch/ Proximity Detector Interface



MTL safety barriers MTL 5511 Switch/ Proximity Detector Interface

 

Copy right © 2018 Power by www.yi-z.cn Management Portal
Contact Person: Jessica Yu;  Tel: 86-027-85508558  Fax: +86 027-85309780
Mobile: 86-15871691193 (Whatsapp & Telegram)  Email: sales1@hkxytech.com; Jackie@hkxytech.com   Skype: Jackie@hkxytech.com

link: www.isolatorbarrier.ltd