MTL5510 safe isolator 4channel DI solid-state ouput
- Product Name:MTL5510 safe isolator 4channel DI solid-state ouput
- Product Number:MTL5510
- Brand:MTL
- Views:452
-
MTL5510 safe isolator 4channel DI solid-state ouput
的详细介绍Product overview
MTL5510 safe isolator 4channel DI solid-state ouput
MTL5510 safe isolator 4channel DI solid-state ouput product made in England
MTL5510 product specification as below
MTL5510 safe isolator 4channel DI solid-state ouput
MTL4510 – MTL5510 SWITCH/ PROXIMITY DETECTOR INTERFACE 4-channel, digital input
The MTLx510 enables four solid-state
outputs in the safe area to be controlled by up to four switches or proximity
detectors located in a hazardous area. Each pair of output transistors shares a
common terminal and can switch +ve or –ve polarity signals. A range of module
configurations is available (see Table 1) through the use of selector switches.
When proximity detector modes are selected, LFD is enabled and the output
switches to OFF if a line fault is detected.
SPECIFICATION
MTL5510 safe isolator 4channel DI solid-state ouput
See also common specification
Number
of channels
4, configured by switches
Location
of switches
Zone 0, IIC, T6 hazardous area Div 1, Group
A hazardous
location
Location of proximity detectors
Zone 0, IIC, T4-6 hazardous area if
suitably certified Div 1, Group A, hazardous location
Hazardous-area
inputs
Inputs conforming to BS EN60947–5–6:2001
standards for proximity detectors (NAMUR)
Voltage
applied to sensor 7 to 9V dc from 1kΩ ±10%
Input/output
characteristics
Normal
phase Outputs closed if input > 2.1mA (< 2kΩ
in input circuit)
Outputs open if input < 1.2mA (> 10kΩ
in input circuit)
Hysteresis: 200µA (650Ω) nominal
Line
fault detection (LFD) (when selected)
User-selectable via switches on the side of
the unit.
Open-circuit alarm on if Iin < 50µA
Open-circuit alarm off if Iin > 250µA
Short-circuit alarm on if Rin < 100Ω
Short-circuit alarm off if Rin > 360Ω
Note: Resistors must be fitted when using
the LFD facility with a contact input
500Ω to 1kΩ in series with switch
20kΩ to 25kΩ in parallel with switch
Safe-area
outputs
Floating solid-state outputs compatible
with logic circuits
Operating frequency: dc to 500Hz
Max. off-state voltage: ± 35V
Max. off-state leakage current: ± 50µA
Max. on-state resistance: 25Ω
Max. on-state current: ± 50mA
LED
indicators
Green: power indication
Yellow: four: on when output active
Red: LFD indication + faulty channel’s
yellow LED flashes
Maximum
current consumption
40mA at 24V (with all output channels
energised)
Power
dissipation within unit: 0.96W
at 24V, with 10mA loads
Safety
description (each channel) Uo=10.5V Io=14mA Po=37mW
Um = 253V rms or dc
Other related models for MTL5500 range as below
MTL5510 safe isolator 4channel DI solid-state ouput
MTL5018AC
MTL5501-SR
MTL5510
MTL5510B
MTL5511
MTL5513
MTL5514
MTL5514D
MTL5516C
MTL5517
MTL5521
MTL5522
MTL5523
MTL5523V – V
MTL5524
MTL5525
MTL5526
MTL5541
MTL5541A
MTL5541AS
MTL5541S
MTL5544
MTL5544A
MTL5544AS
MTL5544D
MTL5544S
MTL5546
MTL5546Y
MTL5549
MTL5549Y
MTL5573
MTL5575
MTL5576-RTD
MTL5576-THC
MTL5581
MTL5582
MTL5582B
MTL5991
MTL5531
MTL5532
MTL5533
MTL5561
MPA5500
MTL5051
MTL5053
MTL5314
MTL5599
MTL5510 safe isolator 4channel DI solid-state ouput
HONGKONG XIEYUAN TECH CO., LIMITED
Telephone:86-027-85508558
Mobile :86-15871691193(Whatapp&Wechat is available)
Skype:xyautomation
E-mail:sales1@hkxytech.com