MTL Safety Barriers Crouse-Hinds Intrinsically Safe Isolators MTL5501SR
- Product Name:MTL Safety Barriers Crouse-Hinds Intrinsically Safe Isolators MTL5501SR
- Product Number:MTL5501SR
- Brand:MTL
- Views:102
-
MTL Safety Barriers Crouse-Hinds Intrinsically Safe Isolators MTL5501SR
的详细介绍MTL Safety Barriers Crouse-Hinds Intrinsically Safe Isolators MTL5501SR
MTL Safety Barriers Crouse-Hinds Intrinsically Safe Isolators MTL5501SR
MTL4501-SR – MTL5501-SR FAIL-SAFE SWITCH/PROXIMITY- DETECTOR INTERFACE with LFD
With the MTLx501-SR, a fail-safe switch/proximity detector located in the hazardous area can control an isolated fail-safe electronic output. The MTLx501-SR also provides relay alarm contacts to signal line-fault conditions. The MTLx501-SR is for use with approved fail-safe sensors in loops that require operation up to SIL3 according to the functional safety standard IEC 61508.
MTL Safety Barriers Crouse-Hinds Intrinsically Safe Isolators MTL5501SR
Number of channels
One
Location of switches
Zone 0, IIC, T6 hazardous area Div. 1, Group A hazardous location
Location of proximity detector
Zone 0, IIC, T4–6, hazardous location Div 1, Group A, hazardous location
Voltage applied to sensor
8.6V dc max from 1kΩ
MTL Safety Barriers Crouse-Hinds Intrinsically Safe Isolators MTL5501SR
Input/output characteristics
Input value in sensor circuits |
Fail–safe output |
Operation |
LFD contacts |
2.9mA < Is < 3.9mA |
ON |
Normal |
CLOSED |
Is < 1.9mA & Is > 5.1mA |
OFF |
Normal |
CLOSED |
Is < 50µA |
OFF |
Broken line |
OPEN |
Rs < 100Ω |
OFF |
Shorted line |
OPEN |
Note: Is = sensor current
MTL Safety Barriers Crouse-Hinds Intrinsically Safe Isolators MTL5501SR
Type
MTL4501SR – MTL5501SR
MTL Safety Barriers Crouse-Hinds Intrinsically Safe Isolators MTL5501SR