Current Location: Home> Product Class> MTL> MTL5500>

MTL Safety Barriers Crouse-Hinds Switch/ Proximity Detector Interface MTL5510B

  • Product Name:MTL Safety Barriers Crouse-Hinds Switch/ Proximity Detector Interface MTL5510B
  • Product Number:MTL5510B
  • Brand:MTL
  • Views:79
你添加了1件商品 查看购物车
简单介绍
MTL Safety Barriers Crouse-Hinds Switch/ Proximity Detector Interface MTL5510B MTL Safety Barriers Crouse-Hinds Switch/ Proximity Detector Interface MTL5510B MTL Safety Barriers Crouse-Hinds Switch/ Proximity Detector Interface MTL5510B

MTL Safety Barriers Crouse-Hinds Switch/ Proximity Detector Interface MTL5510B

的详细介绍

MTL Safety Barriers Crouse-Hinds Switch/ Proximity Detector Interface MTL5510B



MTL Safety Barriers Crouse-Hinds Switch/ Proximity Detector Interface MTL5510B


MTL Safety Barriers Crouse-Hinds Switch/ Proximity Detector Interface MTL5510B


MTL4510B – MTL5510B SWITCH/ PROXIMITY DETECTOR INTERFACE

4-channel, multi-function, digital input


The  MTL4510B  enables  four  solid-state  outputs  in  the  safe  area  to be controlled  by  up  to  four  switches  or  proximity  detectors  located in a hazardous area. Each pair of output transistors shares a common terminal and can switch +ve or –ve polarity signals. A range of module configurations is available (see Table 1) through the use of selector switches. These include start/stop operations and pulse output modes.

MTL Safety Barriers Crouse-Hinds Switch/ Proximity Detector Interface MTL5510B


Specification

Number of channels

4, configured by switches

Location of switches

Zone 0, IIC, T6 hazardous  area Div 1, Group A hazardous location

Location of proximity detectors

Zone 0, IIC, T4-6 hazardous area if suitably certified Div 1, Group A, hazardous location

Hazardous-area inputs

Inputs conforming to BS EN60947–5–6:2001 standards for proximity detectors (NAMUR)

Voltage applied to sensor

7 to 9V dc from 1kΩ ±10%

Input/output characteristics Normal phase

Outputs closed if input > 2.1mA (< 2kΩ in input circuit) Outputs open if input < 1.2mA (> 10kΩ in input circuit)

Hysteresis: 200µA (650Ω) nominal

Line fault detection (LFD) (when selected)

User-selectable via switches on the side of the unit. Open-circuit alarm on if Iin < 50µA

Open-circuit alarm off if Iin > 250µA

Short-circuit alarm on if Rin < 100Ω Short-circuit alarm off if Rin  > 360Ω

Note: Resistors must be fitted when using the LFD facility with a contact input

500Ω to 1kΩ in series with switch 20kΩ to 25kΩ in parallel with switch


MTL Safety Barriers Crouse-Hinds Switch/ Proximity Detector Interface MTL5510B


Type

MTL4510B – MTL5510B

MTL Safety Barriers Crouse-Hinds Switch/ Proximity Detector Interface MTL5510B

 

Copy right © 2018 Power by www.yi-z.cn Management Portal
Contact Person: Jessica Yu;  Tel: 86-027-85508558  Fax: +86 027-85309780
Mobile: 86-15871691193 (Whatsapp & Telegram)  Email: sales1@hkxytech.com; Jackie@hkxytech.com   Skype: Jackie@hkxytech.com

link: www.isolatorbarrier.ltd