MTL5514 1channel DI relay output + LFD alarm product in stock
- Product Name:MTL5514 1channel DI relay output + LFD alarm product in stock
- Product Number:MTL5514
- Brand:MTL
- Views:615
- 
                    
                         
MTL5514 1channel DI relay output + LFD alarm product in stock
的详细介绍Product overview
	MTL5514 1channel DI relay output + LFD alarm product in stock
	
 
	            MTL5514 1channel DI relay output + LFD alarm product in stock
 
	              
 
MTL5514 product specification as below for your reference.
	MTL5514 1channel DI relay output + LFD alarm product in stock
	MTL4514/B – MTL5514 SWITCH/ PROXIMITY DETECTOR
INTERFACE 1-channel, line fault detection, phase reversal
	The MTLx514 enables a safe–area load to be controlled, through a
relay, by a proximity detector or switch located in a hazardous area. Line
faults are signalled through a separate relay and indicated on the top of the
module. Switches are provided to select phase reversal and to enable the line
fault detection.
	SPECIFICATION
	MTL5514 1channel DI relay output + LFD alarm product in stock
	Number of channels :One
	Location of switch 
	Zone 0, IIC, T6 hazardous area 
	Div.1, Group A, hazardous
location
	Location of proximity detector 
	Zone 0, IIC, T4–6 hazardous
area, if suitably certified 
	Div.1, Group A, hazardous
location
	Hazardous–area inputs 
	Inputs conforming to BS
EN60947–5–6:2001 standards for proximity detectors (NAMUR) 
	Voltage applied to sensor 
	7 to 9V dc from 1kΩ ±10%
	Input/output characteristics 
	Normal phase 
	Outputs closed if input >
2.1mA (< 2kΩ in input circuit) 
	Outputs open if input <
1.2mA (> 10kΩ in input circuit) 
	Hysteresis: 200µA (650Ω)
nominal
	Line fault detection (LFD) (when selected) 
	User-selectable via switches
on the side of the unit. Line faults are indicated by an LED. Line fault relay
is energised and channel output relay de-energised if input line-fault detected 
	Open-circuit alarm on if Iin
< 50µA 
	Open-circuit alarm off if Iin >
250µA 
	Short-circuit alarm on if Rin
< 100Ω 
	Short-circuit alarm off if Rin
> 360Ω 
	Note: Resistors must be fitted
when using the LFD facility with a contact input 
	500Ω to 1kΩ in series with
switch 20kΩ to 25kΩ in parallel with switch
	Safe-area output 
	MTL4514 & MTL5514 
	Channel: Single pole relay
with changeover contacts 
	LFD: Single pole relay with
changeover contacts 
	MTL4514B 
	Channel: Single pole relay 
	LFD: Single pole relay
	LED indicators 
	Green: power indication 
	Yellow: channel status, on
when output energised 
	Red: LFD indication, on when
line fault detected 
	Maximum current consumption 
	25mA at 24V dc 
	Power dissipation within unit 
	0.6W at 24V 
	Safety description 
	Uo=10.5V Io=14mA Po=37mW Um =
253V rms or dc
	
 
Other related models for MTL5500 range as below for your reference.
	MTL5514 1channel DI relay output + LFD alarm product in stock
	
	MTL5018AC
	MTL5501-SR
	MTL5510
	MTL5510B
	MTL5511
	MTL5513 
	MTL5514
	MTL5514D
	MTL5516C
	MTL5517
	MTL5521
	MTL5522
	MTL5523
	MTL5523V – V
	MTL5524
	MTL5525
	MTL5526
	MTL5541
	MTL5541A
	MTL5541AS 
	MTL5541S
	MTL5544
	MTL5544A
	MTL5544AS
	MTL5544D
	MTL5544S
	MTL5546
	MTL5546Y
	MTL5549
	MTL5549Y
	MTL5573
	MTL5575
	MTL5576-RTD
	MTL5576-THC
	MTL5581
	MTL5582
	MTL5582B
	MTL5991 
	MTL5531
	MTL5532
	MTL5533
	MTL5561 
	MPA5500
	MTL5051
	MTL5053
	MTL5314
	MTL5599 
	MTL5514 1channel DI relay output + LFD alarm product in stock
	
Contact details
	HONGKONG XIEYUAN TECH CO., LIMITED
	Telephone:86-027-85508558
Mobile :86-158716911930(Whatapp&Wechat is available)
	Skype:xyautomation
E-mail:sales1@hkxytech.com
	
 
     
     
                             
                             
                             
                             
                             
                             
                             
                             
                            