MTL5514D 1channel switch/prox input, dual output relay
- Product Name:MTL5514D 1channel switch/prox input, dual output relay
- Product Number:MTL5514D
- Brand:MTL
- Views:549
- 
                    
                         
MTL5514D 1channel switch/prox input, dual output relay
的详细介绍Product overview
	MTL5514D 1channel switch/prox input, dual output relay
	
 
	           MTL5514D 1channel switch/prox input, dual output relay
 
	           
 
MTL5514D product specification as below for your reference.
	MTL5514D 1channel switch/prox input, dual output relay
	MTL4514D – MTL5514D SWITCH/
PROXIMITY DETECTOR INTERFACE 1-channel, dual output, LFD, phase reversal
	The MTLx514D enables two
safe–area loads to be controlled, through relays, by a proximity detector or
switch located in a hazardous area. When selected, open or short circuit
conditions in the field wiring are detected by the line fault detect (LFD)
facility and indicated on the top of the module. Switches are provided to
select phase reversal and to enable the line fault detection.
	SPECIFICATION
	MTL5514D 1channel switch/prox input, dual output relay
	Number of channels: One 
	Location of switch :
	Zone 0, IIC, T6 hazardous area 
	Div.1, Group A, hazardous
location 
	Location of proximity detector 
	Zone 0, IIC, T4–6 hazardous
area, if suitably certified
	Div.1, Group A, hazardous
location 
	Hazardous–area inputs 
	Inputs conforming to BS
EN60947–5–6:2001 standards for proximity detectors (NAMUR)
	Voltage applied to sensor 
	7 to 9V dc from 1kΩ ±10% 
	Input/output characteristics 
	Normal phase 
	Outputs closed if input >
2.1mA (< 2kΩ in input circuit) 
	Outputs open if input <
1.2mA (> 10kΩ in input circuit) 
	Hysteresis: 200µA (650Ω)
nominal
	Line fault detection (LFD) (when selected) 
	User-selectable via switches
on the side of the unit. Line faults are indicated by an LED. The channel
output relays are de-energised if an input line-fault is detected 
	Open-circuit alarm on if Iin
< 50µA
	Open-circuit alarm off if Iin
> 250µA 
	Short-circuit alarm on if Rin
< 100Ω 
	Short-circuit alarm off if Rin
> 360Ω 
	Note: Resistors must be fitted
when using the LFD facility with a contact input 500Ω to 1kΩ in series with
switch 20kΩ to 25kΩ in parallel with switch
	Safe-area output 
	MTL4514D: two, single pole
relays with normally-open contacts 
	MTL5514D: two, single pole
relays with changeover contacts 
	Note: reactive loads must be
adequately suppressed
	LED indicators 
	Green: power indication 
	Yellow: channel status, on
when output energised 
	Red: LFD indication, on when
line fault detected 
	Maximum current consumption 
	29mA at 24V dc 
	Power dissipation within unit :0.7W at 24V 
	Safety description :Uo=10.5V
Io=14mA Po=37mW Um = 253V rms or dc
	
Other related models for MTL5500 range as below
	MTL5514D 1channel switch/prox input, dual output relay
	MTL5018AC
	MTL5501-SR
	MTL5510
	MTL5510B
	MTL5511
	MTL5513 
	MTL5514
	MTL5514D
	MTL5516C
	MTL5517
	MTL5521
	MTL5522
	MTL5523
	MTL5523V – V
	MTL5524
	MTL5525
	MTL5526
	MTL5541
	MTL5541A
	MTL5541AS 
	MTL5541S
	MTL5544
	MTL5544A
	MTL5544AS
	MTL5544D
	MTL5544S
	MTL5546
	MTL5546Y
	MTL5549
	MTL5549Y
	MTL5573
	MTL5575
	MTL5576-RTD
	MTL5576-THC
	MTL5581
	MTL5582
	MTL5582B
	MTL5991 
	MTL5531
	MTL5532
	MTL5533
	MTL5561 
	MPA5500
	MTL5051
	MTL5053
	MTL5314
MTL5599
	MTL5514D 1channel switch/prox input, dual output relay
	
If you have any other question about MTL5514D, please feel free to send me an inquiry.
Contact details
	HONGKONG XIEYUAN TECH CO., LIMITED
	Telephone:86-027-85508558
Mobile :86-15871691193(Whatapp&Wechat is available)
	Skype:xyautomation
E-mail:sales1@hkxytech.com
	
 
     
     
                             
                             
                             
                             
                             
                             
                             
                             
                            