	The MTLx573
converts a low-level dc signal from a temperature sensor mounted in a hazardous
area into a 4/20mA current for driving a safearea load. Software selectable
features include linearisation, ranging, monitoring, testing and tagging for
all thermocouple types and 2-, 3- or 4-wire RTDs. (For thermocouple
applications the HAZ-CJC plug on terminals 1–3 includes an integral CJC
sensor). Configuration is carried out using a personal computer.
	SPECIFICATION
	MTL5573 1channel Temperature converter, RTD / THC safety barrier
	See also
common specification
	Number
of channels
	One
	Location
of signal source
	Zone 0,
IIC, Hazardous area
	Division
1, Groups A-D, hazardous location
	RTD
excitation current
	200µA
nominal
	Cold
junction compensation, THC input
	Selectable
ON or OFF
	Cold
junction compensation error
	≤ 1.0°C
	Common
mode rejection
	120dB
for 240V at 50Hz or 60Hz
	Series
mode rejection
	40dB for
50Hz or 60Hz
	Calibration
accuracy (at 20°C)
	(includes
hysteresis, non-linearity and repeatability)
	Inputs:
	mV/THC:
± 15µV or ± 0.05% of input value
	(whichever
is greater)
	Pt 100 -
RTD: ± 80mΩ
	Output:
± 11µA
	Temperature
drift (typical)
	Inputs:
	mV/THC:
± 0.003% of input value/°C
	Pt 100 -
RTD: ± 7mΩ/°C
	Output:
± 0.6µA/°C
	Example
of calibration accuracy and temperature drift(RTD input)
	Span:
250Ω
Accuracy: ± (0.08/250 + 11/16000) x
	= 0.1%
of span
	Temperature
drift: ± (0.007/250 x 16000 + 0.6) µA/°C
	=
±1.0µA/°C
	Safety
drive on sensor failure
	Upscale,
downscale, or off
	Early
burnout
	Early
burnout detection for thermocouples (when selected)
	EBD indicated
when loop resistance increase is > 50Ω
	Output
range
	4 to
20mA nominal into 600Ω max.
	Out of
range characteristic - MTL or NAMUR NE43
	Maximum
lead resistance (THC)
	600Ω
with safety drive on sensor failure enabled.
	>10kΩ
with safety drive on sensor failure disabled
	Response
time
	Typical
500 ms
	LED
indicator
	Green:
EBD alarm indication, power and status indication
	Yellow:
alarm indication
	Maximum
current consumption (with 20mA signal)
	50mA at
24V
	Power
dissipation within unit (with 20mA signal)
	1.2W at
24V
	Safety
description
	Refer to
certificate for parameters. Um=253V rms or dc
	Configurator
	A
personal computer running MTL PCS45 software with a
	PCL45USB
serial interface.
	
Other related models for MTL5500 range
	MTL5018AC
	MTL5501-SR
	MTL5510
	MTL5510B
	MTL5511
	MTL5513 
	MTL5514
	MTL5514D
	MTL5516C
	MTL5517
	MTL5521
	MTL5522
	MTL5523
	MTL5523V – V
	MTL5524
	MTL5525
	MTL5526
	MTL5541
	MTL5541A
	MTL5541AS 
	MTL5541S
	MTL5544
	MTL5544A
	MTL5544AS
	MTL5544D
	MTL5544S
	MTL5546
	MTL5546Y
	MTL5549
	MTL5549Y
	MTL5573
	MTL5575
	MTL5576-RTD
	MTL5576-THC
	MTL5581
	MTL5582
	MTL5582B
	MTL5991 
	MTL5531
	MTL5532
	MTL5533
	MTL5561 
	MPA5500
	MTL5051
	MTL5053
	MTL5314
	MTL5599 
	MTL5573 1channel Temperature converter, RTD / THC safety barrier
	
Contact details
	HONGKONG XIEYUAN TECH CO., LIMITED
	Telephone:86-027-85508558
Mobile :86-15871691193(Whatapp&Wechat is available)
	Skype:xyautomation
E-mail:sales1@hkxytech.com
	
 
     
     
                             
                             
                             
                             
                             
                             
                             
                             
                            