MTL5576-RTD 2channel Temperature converter, RTD England origin
- Product Name:MTL5576-RTD 2channel Temperature converter, RTD England origin
- Product Number:MTL5576-RTD
- Brand:MTL
- Views:204
-
MTL5576-RTD 2channel Temperature converter, RTD England origin
的详细介绍Product overview
MTL5576-RTD 2channel Temperature converter, RTD England origin
MTL5576-RTD 2channel Temperature converter, RTD England origin
MTL5576-RTD product specification as below
MTL5576-RTD 2channel Temperature converter, RTD England origin
MTL4576-RTD –
MTL5576-RTD TEMPERATURE CONVERTER RTD/potentiometer input, 2-channel
The MTLx576–RTD
converts signals from resistance temperature detectors (RTDs) mounted in a
hazardous area, into 4/20mA currents for driving safe-area loads. Software
selectable features include input type and characterisation, ranging,
monitoring, testing and tagging. Configuration is carried out using a personal
computer. The MTLx576– RTD is compatible with 2– and 3–wire RTD inputs. The
MTLx576-RTD can also be configured to drive two safe-area loads from a single
input.
SPECIFICATION
MTL5576-RTD 2channel Temperature converter, RTD England origin
See also common
specification
Number of channels
Two
Signal source
2-/3-wire RTDs
to BS 60751
Pt 100, Pt 500,
Pt 1000
Cu-50 &
Cu-53
Ni 100/500/1000
DIN 43760
Location of
signal source
Zone 0, IIC,
T4–6 hazardous area
Division 1,
Group A, hazardous location
Input signal
range
0 to 400Ω (0 to
4000Ω Pt & Ni sensors)
Input signal
span
10 to 400Ω (10
to 1000Ω Pt & Ni sensors)
RTD excitation
current
200µA nominal
Common mode
rejection
120dB for 240V
at 50Hz or 60Hz
Series mode
rejection
40dB for 50Hz
or 60Hz
Calibration accuracy
(at 20°C)(includes hysteresis, non-linearity and repeatability)
Input: ± 80mΩ
Output: ± 16µA
Temperature
drift (typical)
Input: ± 7mΩ/°C
Output: ±
0.6µA/°C
Example of
calibration accuracy and temperature drift(RTD input)
Span: 250Ω
Accuracy: ± (0.08/250 + 16/16000) x 100
= 0.13% of span
Temperature
drift: ± (0.007/250 x 16000 + 0.6) µA/°C
= ±1.0µA/°C
Safety drive on
sensor failure
Upscale,
downscale, or off
Output range
4 to 20mA
nominal into 300Ω max.
Response time
Configurable -
500 ms default
(Accuracy at
100/200ms - contact MTL)
LED indicator
Green: power
and status indication
Yellow: one
provided for channel status
Red: alarm
indication
Power
requirement, Vs with 20mA signal
60mA at 24V
Power
dissipation within unit with 20mA signal
1.4W at 24V
Isolation
Functional
channel–channel isolation for safe and hazardous–area
circuits
Safety
description
Refer to
certificate for parameters.
Um=253V rms or dc
Configurator
A personal
computer running MTL PCS45 software with a
PCL45USB serial
interface.
Other related models for MTL5500 range as below
MTL5018AC
MTL5501-SR
MTL5510
MTL5510B
MTL5511
MTL5513
MTL5514
MTL5514D
MTL5516C
MTL5517
MTL5521
MTL5522
MTL5523
MTL5523V – V
MTL5524
MTL5525
MTL5526
MTL5541
MTL5541A
MTL5541AS
MTL5541S
MTL5544
MTL5544A
MTL5544AS
MTL5544D
MTL5544S
MTL5546
MTL5546Y
MTL5549
MTL5549Y
MTL5573
MTL5575
MTL5576-RTD
MTL5576-THC
MTL5581
MTL5582
MTL5582B
MTL5991
MTL5531
MTL5532
MTL5533
MTL5561
MPA5500
MTL5051
MTL5053
MTL5314
MTL5599
MTL5576-RTD 2channel Temperature converter, RTD England origin
Contact details
HONGKONG XIEYUAN TECH CO., LIMITED
Telephone:86-027-85508558
Mobile :86-15871691193(Whatapp&Wechat is available)
Skype:xyautomation
E-mail:sales1@hkxytech.com