MTL MTL5018AC SWITCH PROXIMITY DETECTOR INTERFACE
- Product Name:MTL MTL5018AC SWITCH PROXIMITY DETECTOR INTERFACE
- Product Number:MTL5018AC
- Brand:MTL
- Views:391
- 
                    
                         
              你添加了1件商品 查看购物车
            
    
            简单介绍
        
        
            MTL MTL5018AC SWITCH PROXIMITY DETECTOR INTERFACE
MTL MTL5018AC SWITCH PROXIMITY DETECTOR INTERFACE
MTL MTL5018AC SWITCH PROXIMITY DETECTOR INTERFACE
        
    MTL MTL5018AC SWITCH PROXIMITY DETECTOR INTERFACE
的详细介绍
                      MTL MTL5018AC SWITCH PROXIMITY DETECTOR INTERFACE MTL5018AC
		
	
        
    Overview
MTL MTL5018AC SWITCH PROXIMITY DETECTOR INTERFACE MTL5018AC
	The MTL5018ac enables two safe-area loads to be controlled by two switches or proximity detectors located in a hazardous area.Two relay outputs are provided. Independent phase reversal control
	allows an alarm condition to be signalled for either state of the sensor.A selectable line fault detect (LFD) facility detects an open or short circuit in either field circuit.
	
		SPECIFICATION
	
	
		See also common specification
	
	
		Number of channels
	
	Two
		MTL MTL5018AC SWITCH PROXIMITY DETECTOR INTERFACE MTL5018AC
	
		Location of switches
	
	
		Zone 0, IIC, T4–6 hazardous area
	
	
		Div. 1, Group A hazardous location
	
	
		Safe-area output
	
	
		Two relays with changeover contacts
	
	
		Hazardous-area inputs
	
	
		Inputs conforming to NAMUR/DIN 19234 standards for proximity
	
	
		detectors
	
	
		Voltage applied to sensor
	
	
		7 to 9V from 1kΩ ±10%
	
	
		Input/output characteristics
	
	Normal (reverse) phase:
		MTL MTL5018AC SWITCH PROXIMITY DETECTOR INTERFACE MTL5018AC
	
		output energised (de-energised) if Iin >2.1mA or Rin <2kΩ
	
	
		output de-energised (energised) if Iin <1.2mA or Rin >10kΩ
	
	
		Hysteresis: 200μA, typical
	
	
		Line fault detection (LFD)
	
	
		User-selectable via switches on the top of the unit. Line
	
	
		faults are indicated by an LED for each channel. A detected line
	
	
		fault de-energises the relay.
	
	
		Open-circuit alarm on if Iin <100μA
	
	
		Open-circuit alarm off if Iin >250μA
	
	
		Short-circuit alarm on if Rin <100Ω
	
	
		Short-circuit alarm off if Rin >360Ω
	
	
		Note: Resistors must be fitted when using the LFD facility with a
	
	
		contact input
	
	
		500Ω to 1kΩ in series with switch
	
	
		20kΩ to 25kΩ in parallel with switch
	
	
		Phase reversal
	
	
		Independent for each channel, user-selectable
	
	
		Relay type
	
	
		Single pole, changeover contacts
	
	
		Note: reactive loads must be adequately suppressed
	
	Relay characteristics
		MTL MTL5018AC SWITCH PROXIMITY DETECTOR INTERFACE MTL5018AC
	
		Response time: 10ms maximum
	
	
		Contact rating: 250V ac, 2A, cosø >0.7
	
	
		40V dc, 2A, resistive load
		
	
			LED indicators
		
		
			Green: power indication
		
		
			Yellow: two: status of each channel (on when outputs are
		
		
			energised)
		
		
			Red: two: LFD indication for each channel (on when line
		
		
			fault detected)
		
		
			Maximum power dissipation
		
		
			<2.5W
		
		
			Isolation
		
		
			250V ac or dc between power supply, hazardous-area circuits
		
		
			and relay outputs
		
		
			Safety description (each channel)
		
		
			10.5V, 800Ω, 14mA, Um= 250V rms or dc
		
		
			Power Supply
		
		
			85 to 265V ac
		
		
			45 to 65 Hz
Contact Information
Email address:Jackie@hkxytech.com jackie2018@126.com
Whatsapp:+86 15717178751
Skype:Jackie@hkxytech.com
Telegram:+86 15717178751
Phone:+86 15717178751
	Contact Information
Email address:Jackie@hkxytech.com jackie2018@126.com
Whatsapp:+86 15717178751
Skype:Jackie@hkxytech.com
Telegram:+86 15717178751
Phone:+86 15717178751
          RELATED PRODUCTS
      
         
     
     
                             
                             
                             
                             
                             
                             
                             
                             
                            